oil immersed 72.5kV Combined Transformer

FOB Reference Price:Get Latest Price
  • >=3 Sets
    $6,500.00
Shipping:
Support Sea freight
Customization:
Customized logo (Min. Order: 6 Sets)
Customized packaging (Min. Order: 6 Sets)

More

Graphic customization (Min. Order: 6 Sets) Less
Report Suspicious Activity
Overview
Quick Details
Place of Origin:
Guangdong, China
Brand Name:
SH
Model Number:
JLD - 72.5
Usage:
Power
Phase:
Single
Coil Structure:
Toroidal
Type:
Oil Immersed Post
Certification:
ISO9001
Product name:
single Phase Transformer
Rated capacity:
500
Frequency:
50Hz/60Hz
Standard:
IEC61869/ICE60044/IEEE/ANSI
Primary voltage:
72.5kV
Application:
Power Grid System
Core material:
copper
Product type:
outdoor Current Transformer
Supply Ability
Supply Ability:
7200 Set/Sets per Year
Packaging & Delivery
Packaging Details
Packing: Goods are packed in wooden cases, with foam inside for protection. And we have a team who is in charge of packing. The team consists of our skilful carpenters and experienced packing designers. These enable our packing reasonable, safe and reliable.
Port
Guangzhou Huangpu port

Oil Immersed 72.5kV Combined Transformer

 Introduction

JLD-72.5 type voltage transformers are oil immersed combined current voltage transformer. The part of VT is imitation shape tank structure. The core was used cold-rolled silicon steel strip to folded. The high voltage coil adopts sectional winding method. The part of CT is inverted structure. The primary conductor passes through the center of the secondary winding and has high measurement accuracy. The secondary windings are protected within the aluminum shield. The rods part of the two body are insulated with capacitive screen structure. They are inside the porcelain bushing and reduce the amount of oil used in the transformer. We select corrugated metal expander as oil temperature variation compensator and can inspect the oil level through window. Outline dimensions drawing and structure shown in Figure 1.

Main Technical Parameters

Table1  Main Technical Parameters

Main Technical Parameters

Type

JLD-72.5

Rated frequency

60Hz

Highest voltage

72.5kV

Insulation level

140/350kV

CT Ith.1s

31.5kA

CT Idyn.

80kA

Rated voltage factor

1.2 con./1.5 30s

Thermal burden

500VA

Instalation

outdoor

Creepage distance

2248mm

CT.

secondary terminal

current rated

accuracy class

burden

1S1-1S5

2S1-2S5

1200/5A

5P20

50VA

1S2-1S5

2S2-2S5

1000/5A

1S3-1S5

2S3-2S5

900/5A

1S1-1S4

2S1-2S4

800/5A

1S2-1S4

2S2-2S4

600/5A

1S3-1S4

2S3-2S4

500/5A

1S4-1S5

2S4-2S5

400/5A

1S1-1S3

2S1-2S3

300/5A

3S1-3S3

200/5A

0.2

50VA

3S1-3S2

100/5A

VT.

secondary terminal

primary voltage

secondary voltage

accuracy class

burden

X1-X2

42000V

120V

0.2

75VA

Y1-Y2

42000V

120V

3P

75VA